Self-operated pressure regulators

2406 - Excess pressure regulator (flanged)

2406

The Type 2406 self-operated excess pressure regulator is used to control the pressure of flammable gases used as a source of energy, e.g. in boilers, driers, vaporizers, heat exchangers, or industrial furnaces. Alternatively, it can control the compressed air supply in process engineering applications.

An additional application of the regulator is the pressure control of inert gas used for inerting or blanketing reaction or storage tanks to protect the product in the tank from oxidation, explosion, or escaping. To achieve economical consumption of the inert gas, its pressure must be controlled to always remain slightly higher than atmospheric pressure while the tank is being filled or emptied.

An excess pressure valve is used to control the upstream pressure (p1) to an adjusted set point. The design of an excess pressure regulator valve is to open when the upstream pressure rises above the set value.

  • Nominal diameters: DN15 to DN50 (1/2" to 2")
  • Pressure classes: PN16 to PN40 (Class 125 to 300)
  • Materials: Cast iron, Cast Steel, Stainless steel
  • Temperature range: -20 to +150°C (-5 to +300°F)
  • Set point range: 0.005 to 10bar (0.075 to 150psi)

Manufactorer: SAMSON

Related documents
Datasheet - DIN T2522EN
Datasheet - ANSIT2523EN
Mounting and operating instructionsEB2522EN
Spare parts EL2522
Drawings - DIN
Drawings - ANSI